| MAIN SPECIFICATIONS OF GENERATOR SETS |
| Diesel Generator Set |
|
| GENSET MODEL NOS. |
C160 |
| Manufacturer |
Yanan |
| Rated speed / frequency |
1500RPM/50Hz |
| Continuous outputï¼KW/KVAï¼ |
160/200 |
| Standby outputï¼KW/KVAï¼ |
176/220 |
| Voltage, Phase and wire |
400V/230V, 3 Phase and 4 Wires |
| Rated power factor |
0.8ï¼laggingï¼ |
| Dimension(L*W*H) (mm) |
3000*1200*1800 |
| Weight(kg) |
2800 |
| Rating Definitions (Operation at Altitude ≤1000m, Ambient temperature ≤ 40â) |
| These ratings are applicable for supplying continuous electrical power (at variable load) in lieu of commercially purchased power. There is no limitation to the annual hours of operation and this model can supply 10% overload power for 1 hour in 12 hours. |
| Diesel Engine |
|
| DIESEL ENGINE MODEL |
6CTAA8.3-G2 (Cummins) |
| Engine Characters |
Water-cooled, 4 cylinders in line, 4-cycle, direct injection |
| The engine outputï¼KWï¼ |
183 |
| Aspiration |
Trubocharged & Aftercooled |
| Bore(mm)×Stroke (mm) |
114X135 |
| Compression ration |
17.0:1 |
| Fuel consumption(L/H) |
39.5(100% load) |
| Displacement(Liters) |
8.3 |
| Exhaust air flow(m3/min) |
216 |
| Compress air flow(m3/min) |
9.6 |
| Exhaust gas flow(m3/min) |
32.58 |
| Exhaust highest temperature |
640â |
| Lub-oil pan capacity(L) |
20 |
| Cooling water capacity(L) |
31 |
| Voltage for start(V) |
24 |
| Instrument for adjusting speed |
Electronically |
| Noise level(A) |
≤70dBA(silent) |
| ALTERNATOR |
ã |
| ALTERNATOR MODEL |
SLG274H |
| Excitation |
Brushless |
| Insulation class |
H |
| Protection class |
IP22 |
| Efficiency |
93.30% |
| Voltage adjust range |
±1% with 4% engine governing |
| Steady state voltage regulation |
≤±1% |
| Voltage Control |
AVR |
| Generating Set Control System |
| AC/DC control panel consisting of: |
| Ä Emergency Stop button |
| Ä Voltmeter and selector switch |
| Ä Ammeter and selector switch |
| Ä Frequency meter |
| Ä Controller Smartgen180 or Smartgen6120C with following (and not restricted to) features: |
| J Start/Stop button |
| J Hour run meter |
| J Monitor engine temperature and provides shutdown protection |
| J Monitor engine speed and provides optional shutdown protection |
| J Monitor oil pressure or level and provides shutdown protection |
| J Alarm output for abnormal operation |
| ã |
ã |